| 士 林 漏 電 斷 路 器 | ||||||||||||||||||||
| 框架容量(AF) | 100 | 100 | 125 | 125 | 250 | 400 | 400 | |||||||||||||
| 型 式 | NV100-MN | NV100-SN | NV125-SN | NV125-HN | NV250-SN | NV400-SN | NV400-HN | |||||||||||||
| 外 觀 |
![]() |
![]() |
![]() |
![]() |
![]() |
|
|
|||||||||||||
| 額定電流 In (A) (AT) (基準周圍溫度40ºC) |
15,20,30,40,50, 60,75,100 |
15,20,30,40,50, 60,75,100 |
15,20,30,40,50, 60,75,100 |
15,20,30,40,50, 60,75,100 |
125,150,175, 200,225,250 |
250,300,350,400 | 250,300,350,400 | |||||||||||||
| 相 線 式 |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w |
1Ø2w,1Ø3w 3Ø3w |
3Ø4w | ||||||
| 極 數(P) | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | 3 | 4 | ||||||
|
額定電壓 V (A.C) |
110 ~ 440 | 110 ~ 440 | 110 ~ 440 | 110 ~ 440 | 110 ~ 440 | 110 ~ 440 | 110 ~ 440 | |||||||||||||
|
高 速 型 |
額定靈敏度電流│∆n(mA) | 30(15,50,100)* | 30(15,50,100)* | 30(15,50,100)* | 30(15,50,100)* | 30,100,500切換 | 30,100,500切換 | 30,100,500切換 | ||||||||||||
|
5│∆n之動作時間(s)以內 |
0.04 | 0.04 | 0.04 | 0.04 | 0.04 | 0.04 | 0.04 | |||||||||||||
|
延 時 型 |
額定靈敏度電流│∆n(mA) | - | - | - | - | 100,300,500切換 | 100,300,500切換 | 100,300,500切換 | ||||||||||||
| 2│∆n之動作時間(s) | - | - | - | - | 0.45,1.0,2.0切換 | 0.45,1.0,2.0切換 | 0.45,1.0,2.0切換 | |||||||||||||
| 2│∆n之 最大不動作時間(s) | - | - | - | - | 0.1,0.5,1 | 0.1,0.5,1 | 0.1,0.5,1 | |||||||||||||
|
漏電表示方式 |
機械按鈕式 | |||||||||||||||||||
外 |
![]() (mm) |
a | 90 | 120 | 90 | 120 | 90 | 120 | 90 | 120 | 105 | 140 | 140 | 185 | 140 | 185 | ||||
| b | 155 | 155 | 155 | 155 | 165 | 257 | 257 | |||||||||||||
| c | 68 | 68 | 68 | 68 | 68 | 103 | 103 | |||||||||||||
| ca | 90 | 90 | 90 | 90 | 92 | 155 | 155 | |||||||||||||
| bb | 132 | 132 | 132 | 132 | 126 | 194 | 194 | |||||||||||||
| aa | 30 | 30 | 30 | 30 | 35 | 44 | 44 | |||||||||||||
| 製品重量(Kg) | 1.5 | 1.8 | 1.5 | 1.8 | 1.5 | 1.8 | 1.5 | 1.8 | 1.7 | 2.3 | 6.6 | 8.4 | 6.6 | 8.4 | ||||||
額 |
CNS 5422 JIS C8371 AC (非對稱值/對稱值) |
*415V *440V |
7.5 | 10 | 18/15 | 30/25 | 30/25 | 35/30 | 50/42 | |||||||||||
|
380V *400V |
10 | 18/15 | 25/22 | 35/30 | 35/30 | 40/35 | 60/50 | |||||||||||||
|
220V *240V |
18/15 | 30/25 | 35/30 | 60/50 | 60/50 | 60/50 | 100/85 | |||||||||||||
|
*100V 110V |
18/15 | 30/25 | 35/30 | 60/50 | 60/50 | 60/50 | 100/85 | |||||||||||||
| IEC 60947-2 EN 60947-2 AC lcu/lcs |
440V |
7.5/3.8 | 10/5 | 15/7.5 | 25/13 | 25/13 | 30/15 | 42/21 | ||||||||||||
|
380V *400V |
7.5/3.8 | 15/7.5 | 22/11 | 30/15 | 30/15 | 35/18 | 20/25 | |||||||||||||
|
220V *230V |
10/5 | 25/13 | 30/15 | 50/25 | 50/25 | 50/25 | 85/43 | |||||||||||||
|
110V |
10/5 | 25/13 | 30/15 | 50/25 | 50/25 | 50/25 | 85/43 | |||||||||||||
| 接線方式 | 壓著端子 | 壓著端子 | 壓著端子 | 壓著端子 | 壓著端子 | 銅接板 | 銅接板 | |||||||||||||
選 購 配 件 |
警報開關(AL) | ● | ● | ● | ● | ▲ | ▲ | ▲ | ||||||||||||
| 輔助開關(AUX) | ● | ● | ● | ● | ▲ | ▲ | ▲ | |||||||||||||
| 電壓跳脫裝置(SHT) | ● | ● | ● | ● | ▲ | ▲ | ▲ | |||||||||||||
| 低電壓跳脫裝置(UVT) | ● | ● | ● | ● | ▲ | ▲ | ▲ | |||||||||||||
| 外部操作把手 | ▲ | ▲ | ▲ | ▲ | ▲ | - | - | |||||||||||||
| 端子隔離蓋 | ▲ | ▲ | ▲ | ▲ | ▲ | ▲ | ▲ | |||||||||||||
| 過載跳脫方式 | 完全電磁式 | 完全電磁式 | 完全電磁式 | 完全電磁式 | 熱動-電磁式 | 熱動-電磁式 | 熱動-電磁式 | |||||||||||||
| 跳脫按鈕 | 有 | |||||||||||||||||||
註1:*額定靈敏度電流 [15,50,100] mA機非一般品,訂貨時需特別註明。
註2:*標明之電壓值,非台灣地區系統電壓,其相對應之啟斷容量僅供參考。
註3:▲為嵌入式可由客戶自行安裝,●附件須由工廠安裝。